Example 3.15: Adiabatic mixing of air with water:  Moist air at 70 °F dry-bulb and 45 °F wet-bulb temperatures is to be processed to a final dew point temperature of 55 °F by adiabatic injection of saturated steam at 230 °F.  The feed rate of dry air is 200 lb/min.  Find the final dry-bulb temperature of the moist air and the steam required in lb/h.

 

Solution 

C                  Find enthalpy of the steam hg = 1157 Btu

ΔhW = hg = 1157 Btu

C                  Use the protractor to join the origin with ΔhW = 1157 Btu and generate a reference line.

C                  Locate State 1 (t = 70 °F, t* = 45 °F) ® W1 = 0.00070 lbw/lba


C                  Draw a line parallel to the reference line passing through State 1 and generate a condition line.

C                  Draw a horizontal line from final dew point td = 55 °F.

C                  Locate intersection of these two lines that defines state 2.

C                  Read properties of state 2.

W2 = 0.00920 lbw/lba

C                  mw = ma(W2 - W1)

= 200´60´(0.00920 - 0.00070) = 102 lb/h