Example 3.15:
Adiabatic mixing of air with water:
Moist air at 70 °F dry-bulb and 45 °F
wet-bulb temperatures is to be processed to a final dew point temperature of 55
°F
by adiabatic injection of saturated steam at 230 °F. The feed rate of dry air is 200 lb/min. Find the final dry-bulb temperature of the
moist air and the steam required in lb/h.
Solution
C
Find enthalpy of the steam hg = 1157 Btu
Δh/ΔW = hg = 1157
Btu
C
Use the protractor to join the origin
with Δh/ΔW = 1157 Btu and generate a reference
line.
C
Locate
State 1 (t = 70 °F, t* = 45 °F) ® W1 = 0.00070 lbw/lba
C
Draw a line parallel to the reference
line passing through State 1 and generate a condition line.
C
Draw a horizontal line from final dew
point td = 55 °F.
C
Locate intersection of these two lines
that defines state 2.
C
Read properties of state 2.
W2 = 0.00920 lbw/lba
C
mw
= ma(W2
- W1)
= 200´60´(0.00920
- 0.00070) = 102 lb/h